Report energy and water use each year, and complete periodic audits and retro-commissioning (A/RCx), which review energy use and tune systems, or get approved exemptions. Los Angeles covers private buildings at least 20,000 square feet. [1, 2, 3, 4, 5]

Last verified Nov 10, 2026 · 8 official sources

Who is covered

≥20,000 ft² · private[2, 3, 5]

Main duty

Benchmark and audit[1, 2, 3, 4]

Next annual benchmark
June 1, 2027

2026 energy and water use.[2]

Next audit / tune-up cohort
December 1, 2026

Building IDs ending 0 or 1.[4]

Audit / tune-up cycle

Every 5 years[4]

City-owned threshold

≥15,000 ft²[1, 5]

On this page

Which buildings does Los Angeles cover?

The Los Angeles Department of Building and Safety (LADBS) runs the city’s energy and water reporting program.

  1. 01

    Check area and ownership.

    Use the City's floor-area measure for coverage. Do not just copy GFA from Portfolio Manager, the energy reporting tool. LADBS's FAQ says coverage uses the California Building Code GFA definition, which treats parking differently. The agency explicitly includes private buildings of exactly 20,000 ft². [2, 5]

  2. 02

    Check use and scope exclusions.

    Multifamily and condos can be covered. The HOA can report a condo. Some production uses, residential hotels, federal-leased buildings and HCAI-regulated facilities have special coverage or exemption instructions. Ask LADBS which category applies. A vacancy or sale alone does not remove yearly reporting. [2, 4]

  3. 03

    Find the LADBS Building ID and status.

    Check the public Benchmark Compliance Status and A/RCx Compliance Status tools linked by LADBS. Ask the agency to resolve multiple IDs. The A/RCx due year now follows your LADBS Building ID. It does not follow the Assessor Identification Number or Portfolio Manager Property ID. [1, 2, 4, 5]

Prepare your Los Angeles filing

  1. 01

    Check both duties and the year due.

    Benchmark each year. A/RCx is due every five years. A benchmark exemption does not always remove A/RCx duties. [2, 4]

  2. 02

    Gather full-year energy and water.

    Gather a full year of energy and water data, including tenant-paid accounts and outdoor water. Include natural gas where used and solar energy generated on-site. LADBS recommends requesting utility data by March 1 to allow time. That is not the yearly filing deadline. [2]

  3. 03

    Set up Portfolio Manager and utility exchanges.

    Enroll with LADWP for combined electricity and water totals, called aggregates. Enroll with SoCalGas for gas. Enter the LADBS Building ID correctly. Check all meters and the full year. [2, 6]

  4. 04

    Register, pay and submit the annual benchmark.

    Register your building for the right benchmark year and pay the yearly registration fee that applies. Use the City's correct Portfolio Manager reporting link. A Portfolio Manager receipt alone does not prove you met City rules. [2]

  5. 05

    Complete A/RCx or get the exemptions that apply.

    A California-licensed architect or engineer with relevant expertise must do or directly supervise the work and declarations. Energy and water are separate parts of compliance. The FAQ says you do not routinely send reports. Signed declarations prove completion. Keep supporting reports available under the record-maintenance rules. [4]

  6. 06

    Check status and keep records.

    Check City status after its stated processing time. Benchmark updates usually take 5–10 business days. Save receipts, fee records, declarations, reports, exemption approvals and utility records. For A/RCx record-keeping, see §91.9707, referenced in LADBS FAQ12. [2, 4]

Your next deadlines

  1. December 1, 2026

    Audit / tune-up: IDs ending 0 or 1

    A/RCx Building IDs ending 0 or 1. [3, 4]

  2. June 1, 2027

    Annual energy and water benchmark

    2026 benchmark on the annual reporting schedule. [2]

  3. December 1, 2027

    Audit / tune-up: IDs ending 2 or 3

    A/RCx Building IDs ending 2 or 3. [4]

Past deadlines and rule changes
  1. October 8, 2026

    The current A/RCx FAQ and alerts are updated, including rules on report validity. [3, 4]

  2. June 1, 2026

    2025 benchmarking due. [3]

  3. February 28, 2023

    The COVID pause on time limits ends, as stated in current FAQs. This relief has ended; it is not an ongoing extension. [2, 4]

  4. November 12, 2020

    Ordinance 186789 takes effect. A/RCx scheduling changes to LADBS Building IDs. [5]

  5. November 22, 2017

    The Ordinance 185198 amendment takes effect. [5]

  6. January 29, 2017

    The original ordinance takes effect, according to LADBS's ordinance history and program page. [1, 5]

Include resident-paid energy and all meters that count

  1. 01

    Request whole-building totals

    Whole-building reports include tenants who pay their own utilities. LADWP and SoCalGas web services can upload combined totals. The LADBS FAQ covers cases with fewer than five tenants who have individual meters. It allows a lease that permits usage access instead of a tenant-consent form. It also describes a specific case where consent remains unresolved. For that case, it allows best-ability comparison estimates for electricity and water usage. [2, 6]

  2. 02

    Include resident-paid energy

    Include resident-paid energy alongside common-area usage. Check which fuels and accounts are in the utility totals.

  3. 03

    Reconcile each meter once.

    Compare resident-paid records with utility totals and common-area meters. Fill gaps without counting the same energy twice.

What Los Angeles requires beyond reporting

EBEWE does not set a general numeric multifamily energy, water or emissions limit. The benchmark FAQ says high energy or water use brings no penalties. Your duties cover reporting and A/RCx. Energy and water performance may help you qualify for specific A/RCx exemptions. [2, 4]

Los Angeles's payments and penalties

Example: an unpaid $202 invoice

Assume an apartment building receives one $202 invoice and does not pay within 30 days. Floor area does not affect this calculation. [4]

Original invoice
$202
Collection charge
$202 × 250% = $505
$707 before later interest or other charges

Unpaid invoice plus collection charge: $707. Later interest and other charges are separate.

A/RCx FAQ17 lists a $202 noncompliance fee under §91.9712. The quoted collection rule adds 250% if you have not paid after 30 days. After 60 days unpaid, 12% yearly interest starts, compounded monthly or for part of a month. Paying does not establish compliance. Further legal action is still possible. Registration and professional costs are separate. Floor area does not multiply this bill. [4]

Check relief and other ways to meet the rules

Apply with proof for the specific energy or water A/RCx exemption. ENERGY STAR certification or NextGen certification may support qualifying energy exemptions. A pending application is not an issued certificate. Current FAQ15 requires A/RCx within the allowed five-year lookback period. It also requires separate building reports. Declarations can be dated no earlier than 90 days before the due date. Each report serves only one compliance year. Ask LADBS for an extension if you have qualifying reasons. Approval does not change certification or exemption lookback conditions. Disaster relief needs proof that you meet its criteria. A county address alone is not enough. [2, 3, 4]

Bring resident-paid usage to your reporting team.

Use available in-unit energy records alongside the separate water and audit records required by EBEWE.

With each resident's permission, Public Grid collects actual monthly in-unit usage where property data sharing is allowed and we handle the resident's account. We export that usage for ENERGY STAR Portfolio Manager, GRESB and BPS or benchmarking reporting. You or your consultant submit the report.

Public Grid is free for owners, managers and residents. Enter your property's address to check electricity coverage.

Unit 305Active

Bills received

STATEMENTUSAGE
Sep 15, 2026Aug 14 – Sep 12471 kWh
Aug 14, 2026Jul 15 – Aug 13618 kWh

Los Angeles EBEWE questions

Need help with in-unit data?

Talk with our team about resident permission, usage records and reporting exports.

Book a demoExplore the blog
What is LA EBEWE?

LADBS runs this program for covered buildings. It requires yearly energy and water reports, plus audits and retro-commissioning (A/RCx) every five years. These review use and tune systems. [1]

What is the 2026 EBEWE deadline?

2025 benchmarking was due June 1, 2026. A/RCx for Building IDs ending 0 or 1 is due December 1, 2026. [3]

Is an apartment building exactly 20,000 ft² covered?

Yes. LADBS explicitly includes private buildings of exactly 20,000 ft². [5]

Does AB 802 filing also satisfy EBEWE?

Use LA's required process. CEC recognizes LA reporting. Filing with the state alone does not establish LA registration, fee payment or A/RCx compliance. [2, 3, 7, 8]

What if residents pay their own utility bills?

Include that energy and water. Use combined utility totals and follow the consent process that applies. [2]

Does paying the $202 fee clear compliance?

No. LADBS explicitly says paying the fee does not establish compliance. [4]